A side-stream filter is installed on a branch of a liquid-cooling loop. Instead of sending the entire coolant flow through the filter, the system routes a controlled portion of the circulating fluid through a separate filtration path and returns it to the loop. This arrangement can support ongoing particle removal while allowing the main circuit to retain a different filtration duty. For CDU replacement-filter buyers, the key question is not simply which micron rating to order. The replacement element must suit the actual branch flow, coolant properties, available pressure differential, contaminant load and filter-housing interface.
What Is Side-Stream Filtration in a CDU Cooling Loop?
In a side-stream arrangement, a branch line takes part of the circulating coolant from the main Technology Cooling System (TCS) loop, passes it through a filter housing and returns the filtered fluid to the loop. Depending on the system design, the branch may use pressure available from the main circulation pump or a dedicated side-stream pump. Isolation valves, flow-control devices and flow or differential-pressure monitoring may also be included.
The side-stream branch is different from a full-flow filter installed directly in the main supply or return line. A full-flow filter processes the entire stream on each pass. A side-stream filter processes only the branch flow, so the whole loop is cleaned progressively as fluid circulates and mixes.

Why Use a Side-Stream Filter Alongside Main-Loop Filtration?
Full-flow filtration and side-stream filtration can serve complementary roles. The main-loop element can be selected to meet the system's required protection at the full circulation rate. A side-stream branch may then provide a finer polishing stage at a lower flow rate, subject to the system designer's requirements and the coolant's compatibility with the selected media.
ASHRAE TC 9.9's 2019 white paper, Water-Cooled Servers: Common Designs, Components, and Processes, describes full-flow, side-stream and combined filtration approaches. It explains that side-stream filtration can use finer media for a fraction of the flow and gives 5% to 10% of total loop flow as a range that is not uncommon in the examples discussed. It also stresses that side-stream flow decay needs to be monitored. This is reference guidance, not a universal design rule for every CDU.
The Open Compute Project's 2025 Modular Technology Cooling System for Cloud Scale paper describes combining 25 µm or even 50 µm inline filtration with side-stream filtration such as below 5 µm as one method of achieving and maintaining TCS cleanliness. The paper presents this as an approach, not a mandatory micron rating or branch-flow percentage for every installation.
These references support a practical principle: a side-stream filter may help maintain circulating-fluid cleanliness, but it does not automatically replace the main-loop filter, commissioning filtration or the protection required at sensitive components. The approved requirements from the CDU, cold-plate, quick-disconnect and coolant suppliers remain the controlling specification.
How to Understand Side-Stream Flow Conditions
1. Confirm the actual branch flow rate
The most important flow value for sizing a replacement side-stream element is the flow passing through that element, not simply the total CDU circulation rate or the pump's nameplate capacity. Obtain the specified minimum, normal and maximum branch flow rates where available. Also confirm whether the branch operates continuously, intermittently or under a control sequence.
A useful way to express the branch flow share is:
For example, if a hypothetical loop circulates 100 L/min and the side-stream branch carries 5 L/min, the branch flow share is 5%. This is an arithmetic example only; it is not a recommended flow rate for a particular CDU or a rating for a Wan-Filter element.
2. Check how the branch receives its driving pressure
If the branch relies on differential pressure available from the main circulation pump, the branch flow may change as pump speed, system resistance, valve positions or filter loading changes. A dedicated pump may provide a different control arrangement, but its operating point and the branch resistance still need to be considered.
Ask the system designer to confirm the available pressure differential across the branch at the required operating conditions. Do not size an element from a single flow figure if the branch flow is expected to vary substantially.
3. Consider coolant viscosity and operating temperature
Flow through a porous or mesh filter medium depends on the fluid as well as the element geometry. Coolant viscosity changes with temperature and formulation. Water, inhibited water and glycol-based mixtures should not be treated as hydraulically identical. A replacement element should therefore be evaluated using the actual coolant composition, concentration and operating-temperature range specified for the loop.
4. Check the branch return point and mixing
The branch take-off and return locations affect how the side-stream circuit interacts with the main loop. The system designer should confirm that the filtered return is properly mixed and that the arrangement does not create an unintended short-circuit path between the branch outlet and inlet. The element supplier needs the resulting flow and pressure conditions, but the overall branch layout belongs to the system designer.
What Does Side-Stream Flow Mean for Particle Removal?
Because only part of the loop passes through a side-stream filter at any moment, particle removal takes place over repeated circulation and mixing. A simplified reference calculation is the nominal loop turnover time:
For illustration, a hypothetical 600 L loop with a 5 L/min side-stream flow has a nominal turnover time of 120 minutes. This does not mean every particle will be removed in 120 minutes. The calculation assumes a simplified well-mixed volume and says nothing by itself about capture efficiency, particle distribution, ongoing contamination, dead legs, filter loading or fluid bypass.
Actual cleanup depends on the filter's particle-retention performance at the relevant particle sizes, how effectively the loop mixes, how contaminants are released, and whether the side-stream flow remains stable. A branch with insufficient or declining flow may take longer to process the loop than the original design estimate suggests.
How to Select a Replacement Filter Element for a Side-Stream Housing
| Specification | Information to confirm | Why it matters |
|---|---|---|
| Branch flow | Minimum, normal and maximum flow through one element | Defines the hydraulic duty of the replacement element. |
| Filtration rating | Micron value, nominal or absolute basis, and any stated beta ratio or test method | Prevents comparing ratings that use different definitions. |
| Pressure-drop allowance | Clean-element pressure drop and the system's replacement or alarm limit, at stated fluid conditions | Helps assess whether the element can operate within the branch's available pressure budget. |
| Coolant | Fluid type, concentration, additives and temperature range | Supports review of media, metal, joining and seal compatibility. |
| Contaminant profile | Particle material, size distribution, likely source and expected loading | Influences media selection, dirt-holding requirements and maintenance planning. |
| Element construction | Woven mesh, sintered mesh, multilayer composite or another specified metal structure | Different constructions have different pore structures, permeability and mechanical characteristics. |
| Housing interface | Overall length, outside diameter, inside diameter, end caps, seals and flow direction | Ensures the replacement fits the existing housing and preserves the intended flow path. |
| Maintenance | Disposable or cleanable design, replacement access and approved cleaning method | Helps align the element construction with the operator's maintenance procedure. |
Choose the filtration rating from the system requirement
A side-stream element may be specified at a finer rating than the main-loop element, but the required value must come from the system's particle-control objective. A micron number alone is incomplete. Confirm whether the rating is nominal or absolute and whether a beta ratio, particle-retention curve or test basis is required. ASHRAE's white paper explains that filter efficiency varies with particle size and uses beta ratio to describe the relationship between particles entering and leaving a filter.
Do not assume that every liquid-cooling loop requires a sub-5 µm or 1 µm element. The appropriate specification depends on the smallest relevant component passage, the approved coolant cleanliness target, the main-loop filtration stage, the side-stream duty and the allowable pressure drop.
Match the media to the coolant and operating duty
Metal filter elements may use woven stainless steel mesh, sintered wire mesh, multilayer composite metal media or powder-sintered metal, depending on the design. Selection should account for the required retention basis, media permeability, particle loading, mechanical support and cleaning expectations. A finer medium is not automatically the best choice if it causes an unacceptable pressure drop or requires impractical replacement frequency.

Confirm the complete wetted-material combination
Compatibility is not determined by the filter medium alone. The element's metal grade, weld or joining areas, end caps, seals and any other wetted parts should be reviewed against the coolant formulation, additives, temperature and system material schedule. Stainless steel grades such as 304 or 316 may be considered where the project specification allows them, but no material should be assumed compatible with every coolant without review.
Monitoring Flow and Differential Pressure During Service
Side-stream filtration only performs its intended role when the branch continues to deliver the required flow. A filter element gradually collecting particles may show an increase in differential pressure, a reduction in branch flow, or both. Looking at only one value can hide a change in operating condition.
ASHRAE TC 9.9 discusses trending flow together with differential pressure to identify declining filter performance and support maintenance planning. OCP's 2025 TCS guidance also highlights differential-pressure sensing across filters and the use of bypass arrangements for operational flexibility. The instrumentation, alarm thresholds and maintenance response should be defined by the system owner or designer.
For replacement planning, confirm the system's approved changeout criterion and whether the branch can be isolated without interrupting critical cooling. A bypass around the housing, if provided, must be understood as part of the system's operating procedure; it should not be assumed that the side-stream filter can be removed or bypassed in every installation.
What to Send a Supplier for a Custom Side-Stream Replacement Element
When requesting a replacement metal filter element, provide as much of the following information as possible:
- The existing filter-element drawing or a clear, dimensioned sample.
- The filter-housing drawing, model or key internal dimensions.
- Required branch flow rate and its operating range.
- Coolant type, concentration, additives and operating-temperature range.
- Required micron rating and whether it is nominal or absolute.
- Available clean pressure-drop information and the system's maintenance or alarm limit.
- Expected particle type, particle-size range and loading conditions.
- Required metal grade, seal material and other wetted-material restrictions.
- Inside-to-out or outside-to-in flow direction, end-cap details and sealing arrangement.
- Whether the element is disposable or intended for an approved cleaning and reuse procedure.
If a drawing is unavailable, photographs of the element and housing, measured dimensions, the original part number and the system specification can help begin a technical review. Final dimensions and requirements should be confirmed before production.

How Wan-Filter Supports Custom Metal Filter Elements
Wan-Filter manufactures customized metal filter elements and filter baskets for industrial filtration applications. For a CDU or liquid-cooling side-stream replacement project, the discussion can focus on the customer's drawing or sample, metal medium, element dimensions, end-cap and sealing arrangement, flow direction and specified operating conditions.
Depending on the project requirements, the available product directions include pleated metal filter elements, sintered wire-mesh elements, multilayer composite metal structures and powder-sintered metal elements. The suitable construction and material must be confirmed against the actual coolant, branch flow, filtration rating and housing design. Wan-Filter supplies filter components; the CDU and side-stream circuit design, operating setpoints and final system qualification remain with the equipment manufacturer and system designer.
Explore the custom metal filter elements, sintered metal filter tubes and industrial filter baskets product pages for related metal filtration formats.
Frequently Asked Questions
What percentage of CDU loop flow should pass through a side-stream filter?
There is no single percentage that applies to every CDU. ASHRAE's 2019 white paper notes that 5% to 10% of total loop flow is not uncommon in the side-stream examples it discusses. The actual branch flow must be set by the system designer based on loop volume, contamination sources, target cleanliness, filter performance and operating constraints.
Can a side-stream filter replace the main CDU filter?
Not automatically. The main-loop filter and side-stream filter can have different duties. The main filter may provide protection on every pass, while the side-stream branch gradually polishes a portion of the coolant. The system designer must define whether both are required.
Should a side-stream filter always use a finer micron rating?
Not always. A finer rating may be selected for a polishing duty, but the choice must balance particle retention, flow, pressure drop, coolant compatibility and element loading. The system's approved specification takes priority over a generic micron recommendation.
How often should a side-stream filter element be replaced?
Replacement timing depends on particle loading, branch flow, differential-pressure trends, coolant condition and the system owner's maintenance criteria. A fixed service interval should not be assumed without operating data.
Can a custom metal element fit an existing side-stream filter housing?
A custom replacement can be manufactured to specified dimensions and interfaces, subject to drawing or sample review. The housing fit, seals, flow direction, media rating and hydraulic requirements all need to be confirmed before production.
Request a Custom CDU Side-Stream Filter Element
If you are sourcing a replacement metal filter element for a CDU side-stream filtration housing, send Wan-Filter your drawing, sample details or current element specifications. Include the branch flow rate, coolant information, filtration rating, dimensions and connection details so the required construction can be reviewed.